25175BREFRIGERANT RECOVERY SYSTEMUSER’S OPERATING MANUALADVANCED TEST PRODUCTS. INC • Miramar, FLTelephone: (954) 499-5400 • Fax: (954) 499-5454 • Tol
HELPFUL HINTS FORREFRIGERANT RECOVERY - cont.This is probably never noticed in charging, because thepressure opens the grommet, but during recovery (o
OPERATING YOUR 25175BDIAGRAM FOR REFRIGERATION RECOVERY1. Inspect the 25175B thoroughly to insure that it is in good operating condition.2. Make sure
SELF PURGING YOUR 25175BPROCEDURE FOR PURGING REMAINING REFRIGERANT FROM THE 25175B1. Close the ports of the system being serviced that are connected
See page 9 of this manual for more information.1. To start you must have a minimum of 5 lbs.of liquid refrigerant in the tank.2. Put RECOVER/PURGE kn
OPTIONAL RECOVERY/TANK PRE OR SUBCOOLING FOR FIXED HOSE SET-UPm A scale must be used to avoidover filling the storage tank.NORMAL RECOVERY:Tank Vapor
REFRIGERANT FLOW DIAGRAM14
1525175B PARTS DIAGRAM25175B PARTS LISTREPLACEMENT KITS & ACCESSORIES*OPTIONAL COMPONENTS FOR 80% CAPACITY TANK SENSING KITPART# DESCRIPTIONKT3302
25175B WIRING DIAGRAM25175B-KT WIRING DIAGRAMINCLUDING OPTIONAL TANK CAPACITY SENSING CIRCUITRY (KIT:KT5001)16
INSTALLATION OF OPTIONAL 80% TANKCAPACITY SENSING COMPONENTS (KIT:KT5001)17Note: ROBINAIR also offers the model, 25175B-KT,with the 80% Capacity Shut
TROUBLESHOOTING YOUR 25175BSAFETY FIRSTRead and understand all safety information containedin this manual before servicing the unit.CONNECT UNIT TO115
FULL ONE YEAR WARRANTYMFG #Robinair products are warranted to be free from defects in workmanship and materials for a period of oneyear from date of p
THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA) REFRIGERANT RECOVERY AND RECYCLING DEVICE ACQUISITION CERTIFICATION FORMEPA regulations have r
INSTRUCTIONS EPA REGIONAL OFFICES21Part 1. Please provide the name, address and telephonenumber of the establishment where the refrigerant
PN/ 100399 Rev.BMADEin the USAMiramar, FLPhone: 954-499-5454Toll Free; 1-800-327-5060Fax: 954-499-5454www.RobinairHVAC.com
TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION 3OPERATING GUIDELINES 4-5CARE AND MAINTENANCE OF YOUR 25175B 5ADDITIONAL RECOVERY TANK INFORMATION 6PURG
m IMPORTANT SAFETY INFORMATION mSAFETY COMES FIRST! Read all safety, operatingguidelines and instructions before operating your25175B.1. CAUTION: ONL
m Before operating the 25175B recovery unit, read the following m1. 25175B IS APPROVED FOR USE WITH THE FOLLOWING CATEGORY III, IV and V REFRIGERAN
NOTE: If there is no liquid in the recovery tank, thenthe cooling method will not work. In this case, use anempty tank that has been fully evacuated t
m Warning: Also read the information pertain-ing to recovery tanks, previously listed underSafety Information and Operating Guidelines.1.CAUTION: NEV
71. Allow the tank to sit undisturbed for 24 hours. This allows the air to rise to the top.2. Connect a manifold to the tank and read the amount of pr
HELPFUL HINTS FORREFRIGERANT RECOVERYPLANNING AHEADKnowing the quantity of refrigerant is important for plan-ning storage requirements, as well as pla